Transformer Calculator

Turns Ratio, Secondary Turns and Primary Current

No ratings yet
Result

—

OneTask is free, with no sign-up, and built by one person.
If this tool saved you time, a coffee helps keep new ones coming.

How the Transformer Calculator works

This transformer calculator works out the turns ratio from the primary and secondary voltages and says whether it steps up or down. Add the primary turns to get the secondary turns, and a load in watts or VA with an efficiency to get the secondary current, primary current, input power and heat lost, plus the impedance ratio for audio and matching work.

A transformer changes AC voltage by winding two coils on one iron core. The ratio of turns sets the ratio of voltages, and because power in roughly equals power out, current changes the opposite way. That is why the grid sends power at hundreds of kilovolts with small currents, and why a doorbell transformer can be tiny while still drawing almost nothing from the mains.

How the transformer calculator works

The formula is Vp ÷ Vs = Np ÷ Ns, so the turns ratio equals the voltage ratio. Secondary turns are Ns = Np × Vs ÷ Vp. The secondary current is the load divided by Vs, and the primary current is the load divided by the efficiency and by Vp. The impedance ratio is the square of the turns ratio, which is how output transformers match speakers to valve amplifiers.

First example. A 230 V to 12 V transformer has a ratio of 19.17 : 1. With 1,150 primary turns the secondary needs 1,150 × 12 ÷ 230 = 60 turns, or 5 turns per volt.

Second example. A 60 W load at 12 V draws 5 A. At 90% efficiency the input is 66.7 VA, so the primary draws 66.7 ÷ 230 ≈ 0.29 A and 6.7 W is lost as heat.

How many amps per kVA at 230 V? 1,000 ÷ 230 ≈ 4.35 A on the primary side.

Turns ratio and current per kVA for common transformers

Use Primary (V) Secondary (V) Turns ratio Primary A per kVA Secondary A per kVA
Doorbell 230 8 28.75 : 1 4.3478 125
Halogen downlight 230 12 19.167 : 1 4.3478 83.333
Doorbell (US) 120 16 7.5 : 1 8.3333 62.5
Thermostat and HVAC control 120 24 5 : 1 8.3333 41.667
Garden lighting 240 12 20 : 1 4.1667 83.333
Irrigation controller 230 24 9.5833 : 1 4.3478 41.667
Site tools (UK) 230 110 2.0909 : 1 4.3478 9.0909
Travel step-down 230 120 1.9167 : 1 4.3478 8.3333
Travel step-up 120 230 1 : 1.9167 8.3333 4.3478
Valve amp output (8 Ω) 4,000 89.4 44.743 : 1 0.25 11.186
Microwave oven (HV) 230 2,100 1 : 9.1304 4.3478 0.4762
Neon sign 230 10,000 1 : 43.478 4.3478 0.1
US pole transformer 7,200 240 30 : 1 0.1389 4.1667
US pad-mount 13,800 480 28.75 : 1 0.0725 2.0833
UK street substation 11,000 433 25.404 : 1 0.0909 2.3095
Australian street substation 11,000 433 25.404 : 1 0.0909 2.3095
UK primary substation 33,000 11,000 3 : 1 0.0303 0.0909
Grid supply point (UK) 132,000 33,000 4 : 1 0.0076 0.0303
Grid (UK supergrid) 400,000 132,000 3.0303 : 1 0.0025 0.0076
US transmission 345,000 138,000 2.5 : 1 0.0029 0.0072
Power station generator step-up 23,500 400,000 1 : 17.021 0.0426 0.0025
Laptop charger (inside the brick) 340 20 17 : 1 2.9412 50

Tips and pitfalls

FAQ

How do you calculate a transformer turns ratio?

Divide the primary voltage by the secondary voltage. A 240 V to 24 V transformer has a ratio of 10 : 1, so for every 10 turns on the primary there is one on the secondary. The same ratio applies to the number of turns, so a 500-turn primary needs a 50-turn secondary.

How do you calculate transformer primary current?

Divide the load power by the efficiency and then by the primary voltage. A 100 W load at 95% efficiency on a 230 V supply draws 100 ÷ 0.95 ÷ 230 ≈ 0.46 A. Ignoring efficiency gives a slightly low answer, which matters when sizing fuses and cables.

What is the difference between a step-up and step-down transformer?

A step-down transformer has fewer turns on the secondary, so the output voltage is lower and the current higher. A step-up has more secondary turns, raising the voltage and lowering the current. Power stations step up for transmission and local substations step back down.

Why is a transformer rated in VA instead of watts?

The heat in the windings depends on the current, whatever the power factor of the load. VA is volts times amps, so it captures that current directly. A load with a poor power factor can draw 1,000 VA while delivering only 700 W, and the transformer has to handle the full 1,000 VA.

What is the impedance ratio of a transformer?

The impedance ratio is the square of the turns ratio. An output transformer with a 22.4 : 1 ratio makes an 8 Ω speaker look like about 4,000 Ω to a valve amplifier. This is how transformers match a load to a source so that the most power is transferred.

See also: all Electronics tools, Physics, Chemistry.